4-20mA Power Plant Components Dry Type Transformer Temperature Controller RS485 Communication
Product Details
Power Plant Components Transformer Controller
,RS485 Power Plant Components
,RS485 dry type transformer temperature controller
DINKONDA GLOBAL Power Plants Special LD-B10-10 Series Dry-type Transformer Intelligent Temperature Controller, RS485 Communication And Standard 4-20mA Analog Current Output Function
Product Introduction
The LD-B10-10 series dry-type transformer temperature controller (referred to as the temperature controller) is an intelligent temperature controller designed specifically for the safe operation of dry-type transformers. It is designed and manufactured in accordance with the industry standard JB/T7631-2016<<Electronic Temperature Controllers for Transformers>>. Equipped with high-performance microcontrollers and other interface circuits, it has the functions of measuring, displaying, and real-time monitoring the temperature of transformer windings and iron cores; It has the functions of automatic start of cooling fan, switching between manual/automatic control of fan, timed start stop control of fan, and remote transmission of fan operation signals; It has the functions of over temperature alarm output, over temperature trip, and iron core alarm output, which can effectively distinguish fault signals such as sensor open circuit, ensuring that the temperature controller will not mistakenly send over temperature alarm or over temperature trip signals when the transformer is stopped or powered on; Equipped with a "black box" function that stores the measured values of each channel in case of power failure; Equipped with temperature simulation output function; Equipped with RS485 communication and standard 4-20mA analog current output function, it enables remote temperature and status monitoring.
Technical Indicators
1. Working environment
Environmental temperature: -25 ° C~55 ° C;
Relative humidity:<95% (25 ° C);
Power frequency: 50Hz or 60Hz (± 2Hz);
Working voltage: AC220V (+10%, -15%);
(Unless otherwise specified during ordering, AC22OV shall prevail)
2. Measurement range
-30.0°C~240.0°C;
3. Measurement accuracy
Accuracy Level: Level 1 (Temperature Controller Level 0.5, Sensor Level B)
Resolution: 0.1 ° C;
4. Power consumption of thermostat
≤8W;
5. Contact capacity
Total capacity of fan contacts: 6A/250VAC (cos=0.4) (single-phase fan);
Control output capacity: 5A/250VAC; 5A/30VDC (resistive);
6. Design and production standards
JB/T7631-2016 "Electronic Temperature Controllers for Transformers"
ISO 9001:2015 Quality Management System Requirements.

Wiring Diagram


Inquiry?
Have A Question? Fill Out The Form Below And We Will Get Back To You As Soon As Possible.